Product Line

Vacuum Pump System
Vacuum Pump System

Vacuum Pump System

Description
  1. The machine which is automatic switched operation system with dual machines.
  2. The main and vice machine of the system exchange operation once in every six hours in order to extend the service life of equipment.
  3. Load operation. When the machine A (main machine) operates after two minutes but the pressure has not been able to reach the set value (-600mmHg), then machine B (vice machine) will start automatically. So the pressure can quickly reach to the set value (-600mmHg) and then it will shut down automatically.
  4. After six hours the machine B (main machine) runs two minutes but the pressure has not been able to reach to the set value (-600mmHg), then machine A (vice machine) will start automatically. So the pressure can quickly reach to the set value (-600mmHg) and then it will automatic shut down.
  5. The system installed running timer. In first time use, it should be changed oil (R68) at the 500 hours or 2 months. And later the oil (R68) change in every 1000 hours of operation or in every 6 months.


Vacuum Pump System (671 KB)
Features

Loading...